Top Banner

XQC1200 Mobile Generator Sets

This rental generator set extends the Caterpillar line of rental power options improving efficiency and reduced owning and operating costs. The XQC1200 is equipped with an enhanced control system, designed to reduce installation and startup time. It is configured to switch between 50 and 60Hz ratings at the press of a button. The control system features plant control programming and simulation, allowing complete system testing prior to generator set startup. Advanced product autonomy and monitoring capabilities reduce on-site manpower support requirements, minimize operator exposure to hazards, and permit site performance and maintenance data to be viewed, archived, and analyzed conveniently. Ideal in a stand-alone environment, combined with dozens of units in a power plant solution, or supporting utility systems worldwide.

XQC1200

GET A QUOTE

A sales engineer replies within one working day.

The Catยฎ XQC1200 is built for reliable performance in the electric power range, backed by Al-Bahar's regional service and support network.

Rating
1150kW (1438 kVA) Continuous
Frequency
50/60 Hz
Voltage
230 - 480 V
Engine
Cat 3512C
Download Brochure
  • Specifications
  • Features
  • Standard Equipment

Specifications

Generator Set specifications
Rating 1150kW (1438 kVA) Continuous
Frequency 50/60 Hz
Voltage 230 - 480 V
IPP Overload 50Hz 1205 ekW (1506 kVA)
IPP Rated 60Hz 1260 ekW (1575 kVA)
IPP Overload 60Hz 1330kW; (1662KVA)

Features

Rental Ready

Extensive range of rental ready features to meet job requirements and applications.

Fuel/Emissions Strategy

Low BSFC and Low Emissions* ratings, switchable via Cat Electronic Technician (ET) * Does not conform to EPA/EU emissions standards

Reliable, Fuel Efficient Cat Diesel Engine

The compact, four-cycle Cat 3512C turbocharged-aftercooled (SCAC) diesel engine provides proven durability and dependability Best-in-class fuel economy Fuel system operates on a variety of fuels 50/60 Hz switchable with neither software re-flashing, nor iron changes required Other engine features include: electric fuel priming, individual cylinder temperature monitoring, and extended filter change intervals

Cat EMCP Control Panel

EMCP 4.3 control panel offers engine and generator monitoring and protection On-Package Auto Paralleling Controls AGC-4 provides paralleling, load sharing, VFD control, and additional generator protection

Cat Generator

Cat SR500 generator designed to match the performance and output characteristics of the Cat Gas engine. Class H insulation operating at Class F temperature for extended life Coastal insulation protection and anti-condensation space heaters Integrated Voltage Regulator (IVR) for fast response in demanding applications

Standard Equipment

Cat 3512C heavy duty diesel engine
  • Heavy duty, dual element, PowerCore air cleaners with service indicators
  • Secondary fuel filters
  • Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil
  • Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
  • Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
SR5 Generator
  • Double-bearing, SR-5 generator with anti-condensation space heaters (1.2 kW, 480VAC)
  • Brushless, random-wound, permanent magnet excited, thouree-phase, 4-lead design
  • Class H insulation operating at Class F temperature for extended life
  • Cat Integrated Voltage Regulator (Cat IVR)
  • Stator winding and bearing temperature sensors and RTD module
20' ISO high-cube container, 9-High stackable, CSC certified
  • Hinged, radiator air intake louvers
  • Sound-attenuated engine room air intake louvers with foldable awnings that double as shipping covers
  • Two (2) lockable personnel doors with panic releases
  • Interior walls and ceilings insulated with 50 mm of acoustic paneling
  • Side bus bar access door with external access load cable connections
Cooling
  • Cooling package provides 40ยฐC (104F) ambient capability at 50 Hz, or 42ยฐC (108F) capability at 60 Hz at the IPP Rating at 750m (2,460 ft) above sea level
  • Vertical, non-stacked radiator cores with dimpled fins and vertical air discharge
  • Variable frequency fan drive with smart fan control
  • Cat Extended Life Coolant (ELC)
Generator Controls and Protection
  • EMCP 4.3 generator set mounted controller
  • Automatic start/stop with cool down timer
  • Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
  • AGC-4 provides voltage and frequency adjust, base load / PF / load sharing / synchouronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level Indications & alarms, and fuel tank fuel transfer control
  • Reverse compatibility for interface to legacy power modules
Quality
  • Factory testing of complete power module
  • CE Certified, NEMA, ISO and IEEE standards
  • O&M manuals