Maximum Rating | 400 ekW (500 kVA) |
Minimum Rating | 400 ekW (500 kVA) |
Emissions/Fuel Strategy | U.S. EPA Tier II Nonroad Mobile Emissions Certified. Available for NSPS compliance via Design to Order process |
Aspiration | Turbocharged-Aftercooled |
Manifold Type | Watercooled |
Bore | 137 mm |
Stroke | 164 mm |
Displacement | 29 l |
Engine Control and Protection | ADEM A4 |
Generator Set Control | EMCP 4.4 Control Panel |
Generator | SR4B |
Frequency - Speed | 60 Hz (1800 rpm) |
Fuel | CNG, LNG, field gas, natural gas |
Lube Oil System - Refill | 170 l |
Cooling System - Engine | 55.5 l |
Length | 5842 mm |
Width | 2261 mm |
Height | 2599 mm |
Weight | 8950 kg |
Air cleaner — intermediate duty, dry
Air cleaner rain cap
Air cleaner service Indicator
High ambient radiator design for gas fuel applications
Stacked aftercooler and jacket water core
Metal top and bottom tanks
Coolant drain
Fan and belt guard
Coolant level sensor
Exhaust manifolds — water cooled
Exhaust elbow and flex fitting — 127 mm (5 in)
Residential grade muffler
Three-way catalyst
Muffler mounting structure
Gas pressure regulator — requires 10.3-34.5 kPa (1.5-5 psi) gas
Natural gas carburetor
Air Fuel Ratio Control
Rated for continuous duty — 10% oversize
Class H insulation
Permanent magnet
Random wound
240 VAC space heater
Coastal insulation protection
IP23 protection
Cat Digital Voltage Regulator
Electronic governing ADEM A4
Electronic diagnostics and fault logging
Momentary start/stop logic
High temperature braided engine harness with 70-pin customer connector and service tool connector
Crankcase breather, top-mounted
Oil filter, spin-on, left-hand service
Dipstick, left-hand service
Oil pump — gear-driven
Oil cooler
Heavy-duty welded steel base designed for the oilfield
Base design optimized for loading, transport, and unloading
The following parameters include alarm and shutdown:
Jacket water heater
24V starting motor
24V, 45-amp charging alternator
1 micron gas filter