Minimum Rating | 730 ekW (913 kVA) |
Maximum Rating | 940 ekW (1175 kVA) |
Frequency | 60hz |
Speed | 1800 rpm |
Emissions/Fuel Strategy | EPA Tier III |
Aspiration | Turbocharged and aftercooled |
Bore | 145 mm |
Stroke | 162 mm |
Displacement | 32.1 l |
Governor Type | Electronic |
Fuel System | MEUI |
Engine Model | Vee-12, 4-stroke-Cycle-Diesel |
Width | 1528 mm |
Height | 1667 mm |
Weight - Estimated | 7131 kg |
Length | 162.8 in/4271 mm (minimum), 175.3 in/4452 mm (maximum) |
Excitation | Permanent magnet |
Number of Poles | 4 |
Number of Bearings | 2 roller bearings |
Number of Leads | 6 |
Insulation | Class H |
IP Rating | 23 |
Voltage Regulator | CDVR |
Separate circuit after-cooled (SCAC)
Turbocharger, jacket water cooled
Turbocharger inlet, 152 mm (6 in) OD straight connection
If an EMCP panel or MGCP option is not chosen as optional equipment, then start/stop controls must be provided by the customer
Electronic diagnostics and fault logging
Engine Protection Mode for extended ambient conditions
Electronic fuel/air ratio control
Separate Circuit After-Cooling (SCAC) for Heat Exchanged (HEX) & Keel cooled engines
Jacket Water (JW) and SCAC Heat Exchangers Shell & Tube for HEX cooled engines
SCAC pump, gear driven
Jacket water pump, gear driven
Sea water pump, bronze impeller, gear driven, for HEX cooled engines only
Jacket water HEX with Sea water pump Connections: 76.2 mm (3in) ID Standard
4 Bolt ANSI Flange Connection
Jacket water HEX without Sea water pump Connection: 2.5" hose barb connection (inlet), 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange (outlet)
Keel Connections: 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange Connection
SCAC and JW shunt tanks for maintaining proper Pump inlet pressures
Water-cooled exhaust manifold & turbocharger
4 Bolt 130 mm (5.12 in) diameter flanged outlet
Flywheel Housing, SAE No. 0
Flywheel, 18 inch, 136 teeth
SAE standard rotation
Duplex Fuel Filters, Spin-on, RH service
Fuel connections size: Supply JIC 37 Deg -10 (7/8-14), Return JIC 37 Deg -8 (3/4-16)
Plate-type fuel cooler installed behind Aftercooler Shunt Tank
Fuel transfer pump, gear driven
Manual fuel priming pump
SR5 form wound
2 roller bearings
Permanent magnet excitation
4 pole, 6 leads, Series Star connected
Caterpillar's Digital Voltage Regulator (CDVR)
Marine Class H insulation, Class F temperature rise
Surface mounted platinum (PT100) 3-wire RTDs, 2 per phase on stator and one each on support bearings
Anti-condensation space heaters (2 elements - 240 VAC, 1000 Watts
IP23 Protection suitable for use with Fixed Water Based Local Application Fire Fighting Systems (FWBLAFFS)
System IV insulation for harsh environment protection
Simplex oil filters, RH service
Deep sump oil pan
RH service oil filler locations
RH service dipstick
Oil pump, gear driven
Formed C-channel rails, 300mm (11.81in) height
Six shipped loose combined helical spring/rubber
isolators for installation below package base
Front Damper guard
Common electrical bondng point on HEX and KEEL cooled engines
Remote panels
MCS Controller
Power analyzer module
Oil level, exhaust temperature, air starting pressure, heat exchanger pressure sensors
Dry Elbows
Flexible Fitting
Flange
Muffler
Muffler Spark Arresting
Rain Cap
Air Inlet Cleaner
Closed Crankcase Ventilation
Air inlet adapter
Battery Chargers, Charging Alternators
Load Sharing Attachment
Water Separator
Duplex Oil Filters, Sump Pump
Fuel and Oil Shielding
Electric Starting Motors - Single 24 Volt
Air Starting Motor
Dual Starting Motors (Electric and Air)
Air Start Accessories
Starting Aids - JW Heaters
Battery Sets - 24 Volt - Dry