Descriptions
Manufacturer:
Caterpillar
Product Family:
Power Modules (obs)
Model:
3516
Year:
2007
SMU/Hrs:
22964
Location:
UAE
Serial number:
ZAP00615
Configuration | Floor Standing modular switchgear paralleling system (Master Breaker Panel for the first 2 gensets, separate structures for up t |
Modes of Operation | Emergency Standby with redundant master control. Utility paralleling, peak shaving, and closed transition to/from Generator Powe |
Application | LV only (208V - 480V) |
ANSI Protective Devices | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
ANSI Protective Devices | (Utility Grade) SR-750 / SEL-351S, 25, 27/59, 81 O/U, 32,47 (Industrial Grade) 15 |
Certifications | UL891 |
Control Panel Enclosure | NEMA1 |
Operating Temperature | 0°C to 55°C |
Storage Temperature | -20°C to 60°C |
With electrically operated generator circuit breakers, lugs or cross-bus, and genset controls
Allows user to return system to automatic in the event of a touchscreen failure
2 discrete inputs and 3 discrete outputs programmable from the HMI
With breaker position indications, circuit breaker control switch, generator controller, and user programmable logic I/O
With closed transition soft transfer and utility control for 1 LV circuit breaker, utility grade protective relay, utility close lockout switch, breaker position indications, and circuit breaker control switch
Provides additional discrete synchronization protection
Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
With I/O module for control of up to 3 circuit breakers
Each slave panel contains 3 distribution breakers