Descriptions
Manufacturer:
Caterpillar
Product Family:
Power Modules (obs)
Model:
3516
Year:
2007
SMU/Hrs:
22964
Location:
UAE
Serial number:
ZAP00615
Rating Range | Switch Dependent |
Transfer Type | Application Dependent |
Switch Type | Application Dependent |
Undervoltage dropout for source 1 and source 2 | 75-98% of nominal |
Undervoltage restore for source 1 and source 2 | 85-100% of nominal |
Underfrequency dropout for source 1 and source 2 | 90-100% of nominal |
Delay for engine cool down (U) | 0-60 minutes |
Delay transfer to nonpreferred source (W) | 0-5 minutes |
Delay NeutralTransition time delays (DT,DW) | 0-10 minutes |
Storage temperature | (-30?C - 75?C ), -22?F - 167?F |
Operating temperature (ambient) | 40 - 400 amp molded shell (-20?C to 65?C) , -4?F to 149?F <br>40 - 4000 amp all others (-20?C to 60?C), -4?F to 149?F |
UL, CSA and IEC listed
Ringing wave immunity per IEEE 472(ANSIC37.90A)
Conducted and Radiated Emissions per EN55022Class B (CISPR11) (Exceeds EN55011 & MILSTD461 Class 3)
ESD immunity test per EN61000-4-2 Class B(Level 4)
Radiated RF, electromagnetic field immunitytest per EN61000-4-3 (ENV50140) 10v/m
Electrical fast transient/burst immunity test perEN61000-4-4
Surge immunity test per EN61000-4-5 IEEE C62.41
Conducted immunity test per EN61000-4-6(ENV50141)
Voltage dips and interruption immunity EN61000-4-11
Multipurpose display: LEDs for continuous monitoring of switch position and source availability; a four line by twenty character LCD display for settings, functions, programming and annunciation
Through-the-door programming and display
Simplified keypad entry – menu-driven system is designed for ease of use
Built-in diagnosis with displays for ease of troubleshooting
Weather and tamper resistant touchpad
Built-in programmable exerciser uses separate microcontroller with independent battery back-up to serve as clock/calendar – battery failure will not affect switch operation
User settings are unaffected by power outages
Separate line voltage components for controller isolation
Inputs are optoisolated for high electrical immunity to transients and noise
Built-in electrical operator protection
Watchdog circuit for microprocessor operation
Source connection and transfer data logging