Descriptions
Manufacturer:
Caterpillar
Product Family:
Power Modules (obs)
Model:
3516
Year:
2007
SMU/Hrs:
22964
Location:
UAE
Serial number:
ZAP00615
Rating Range | 120 to 600V, single phase and three phase @ 50/60 Hz |
Transfer Type | Switch application dependent |
Switch Type | Switch application dependent |
Input control voltage | 65 to 145 Vac 50/60 hZ |
Voltage measurements of Utility | Source 1 VAB Source 2 VAB<br>Source 1 VAC Source 2 VBC<br>Source 1 VCA Source 2 VCA |
Voltage measurement range | 0 to 790 VAC rms (50/60 Hz) |
Voltage measurement accuracy | +/-2% of nominal input voltage |
Frequency measurements of | Source 1 and Source 2 |
Frequency measurement range | 40 Hz to 70 Hz |
Frequency measurement accuracy | +/- 0.1 Hz |
Undervoltage dropout | 50% to 90% of nominal voltage |
Undervoltage pickup | (Dropout +2%) to 99% of the nominal system voltage |
Underfrequency dropout range | 90 to 97% of the nominal system frequency |
Underfrequency pickup range | (Dropout +1 Hz) to 99% of the nominal system frequency |
Overfrequency dropout range | 103 to 110% of the nominal system frequency |
Overfrequency pickup range | 101% to (dropout - 1 Hz) of the nominal system frequency |
Operating temperature range | -20 to 70 degree C (-4 to +158 degree F) |
Storage temperature range | -30 to 85 degree C (-22 to +185 degree F) |
Operating humidity | 0 to 95% relative humidity (noncondensing) |
Operating environment | Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons |
Generator start relay | 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load |
K1, K2 relays | <br>10A, 1-3 hp @ 250 Vac</br><br>[email protected] Vdc</br> |
Applicable testing | UL-recognized component<br>Meets intent of UL 991 & UL 1008<br>Meets IEC 1000-4-2, 1000-4-3, 1000-4-4 |
Applicable testing continued | 1000-4-5, 1000-4-6, 1000-4-11<br>CISPR 11, Class A<br>FCC Part 15, Class A<br>CSS 22.2-178 |
Enclosure compatibility | NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-300+ faceplate |