• Banner
Switchgear and Paralleling Controls

Caterpillar and your local Cat® Dealer are ready for all your power generation demands. From diesel and gas generator sets to uninterruptible power supplies, automatic transfer switches and electrical switchgear, our experienced worldwide dealer network can deliver the power systems and support you need.

Engine Paralleling and Integration Control (EPIC)

  • Specification Summary

  • Configuration Remote modular paralleling control system (Master Control Panel for the first 2 gensets, separate add-on control panels for up 8
  • Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Powe
  • Application LV and MV (208V-27kV)
  • ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
  • Specification Sheet

    Download

Product Details

Technical Summary

Configuration Remote modular paralleling control system (Master Control Panel for the first 2 gensets, separate add-on control panels for up 8
Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Powe
Application LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications UL / cUL 508A
Control Panel Enclosure NEMA 12
Operating Temperature 0°C to 55°C
Storage Temperature -20°C to 60°C
  • Master Control Panel (MCP), for first 2 gensets, with lockable front door
    • 12" Graphical Color Touchscreen display (HMI)
      • Instant Auto Selector Switch
        •  Allows user to return sysem to automatic in the event of a touchscreen failure
      • Allows user to return sysem to automatic in the event of a touchscreen failure
        • Top or Bottom Conduit Access ( for MCP) for interconnect control wiring access
          • Generator Control Panel (for 3-10 gensets)
            •  With breaker position indications and circuit breaker control switch
          • Utility Control Panel (for utility paralleling and control)
            •  With utility close lockout switch, breaker position indications, and circuit breaker control switch
          • Supplemental Hardware 25 Device
            •  Provides additional discrete synchronization protection
          • Data Table Interface
            •  Accommodates interface with a building management system
          • Accommodates interface with a building management system
            • Generator Demand Priority Control
              •  An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity
            • An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity
              Built for it