ATS ATC Breaker / Contactor

Caterpillar and your local Cat® Dealer are ready for all your power generation demands. From diesel and gas generator sets to uninterruptible power supplies, automatic transfer switches and electrical switchgear, our experienced worldwide dealer network can deliver the power systems and support you need.

ATC-100 CONTROLLER

The ATC-100 is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels.The ATC provides both fixed and jumper-selectable settings to allow for a range of applications. It operates from all system voltages between 120 and 480 Vac, single-phase and three phase at 50 or 60 Hz. The ATC-100 monitors the condition of the three-phase line to line voltage and the frequency of both the utility and generator power sources. It can also be set up for single-phase operation. The ATC-100 provides the necessary intelligence to ensure that the transfer switch operates properly through a series of selectable sensing and timing functions.

  • Specification Summary

  • Rating Range 120 to 480V, single phase and three phase @ 50/60 Hz
  • Transfer Type Switch application dependent
  • Switch Type Switch application dependent
  • Input control voltage 95 to 145 Vac 50/60 Hz
  • Specification Sheet

    Download

Product Details

Technical Summary

Rating Range 120 to 480V, single phase and three phase @ 50/60 Hz
Transfer Type Switch application dependent
Switch Type Switch application dependent

ATC Controller Specifications

Input control voltage 95 to 145 Vac 50/60 Hz
Voltage measurements of Utility V<sub>AB</sub> generator V<sub>AB</sub><br>V<sub>BC</sub> generator V<sub>BC<
Voltage measurement range 0 to 575 Vac rms (50/60 Hz)
Voltage measurement accuracy ± 1% of full scale
Frequency measurements of Generator
Frequency measurement range 40 Hz to 70 Hz
Frequency measurement accuracy ±0.3 Hz over the measurement range
Undervoltage dropout 80% of the nominal system voltage
Undervoltage pickup 90% of the nominal system voltage
Underfrequency dropout range 90% of the nominal system frequency
Underfrequency pickup range 95% of the nominal system frequency
Overfrequency dropout range 115% of the nominal system frequency
Overfrequency pickup range 110% of the nominal system frequency
Operating temperature range –20 to +70°C (–4 to +158°F)
Storage temperature range –30 to +85°C (–22 to +185°F)
Operating humidity 0 to 95% relative humidity (noncondensing)
Operating environment Resistant to ammonia, methane, nitrogen, hydrogen and hydrocarbons
Generator start relay 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
K1, K2 relays <br>10A, 1–3 hp @ 250 Vac</br><br>10A@30 Vdc</br>
Applicable testing UL-recognized component<br>UL 1008, UL 991 Environmental IEC 61000-4-2, 61000-4-3, 61000-4-4,
Applicable testing continued 61000-4-5, 61000-4-6, 61000-4-11<br>CISPR 11, Class B<br>FCC Part 15, Class B<br>CSS 22.2-178
Enclosure compatibility NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-100 faceplate